Restaurant Fire Suppression Systems
|
|
The Ansul R-102 Restaurant Fire Suppression System is an automatic, pre-
engineered, fire suppression system designed to protect the following areas associated
with cooking equipment; ventilating equipment including hoods, ducts, plenums, and
filters; fryers; griddles and range tops; upright, natural charcoal, or chain-type
broilers; electric, lava rock, mesquite or gas-radiant char-broilers and woks. The
system is UL Listed under UL standard 300.
|
|
|
|
|
The system is ideally suitable for use in restaurants, hospitals, nursing
homes, hotels, schools, airports, and other similar facilities.
Use of the R-102 system is limited to interior applications only. The regulated
release and tank assemblies must be mounted in an area where the air temperature will not
fall below 32°F (0C) or exceed 130°F (54C). The system must be designed and installed within
the guidelines of the UL Listed Design, Installation, Recharge, and Maintenance Manual.
|
|
|
|
|
|
- UL Listed - Meets Requirements of UL 300
- Low pH Agent
- Proven Design
- Reliability with a Mechanically Activated Cartridge System
- Aesthetically Appealing
|
|
|
|
|
The restaurant fire suppression system is a pre-engineered, wet chemical,
cartridge- operated, regulated pressure type with a fixed nozzle agent distribution
network. It is listed with Underwriters Laboratories, Inc. (UL).
The system is capable of automatic detection and actuation and/or remote manual
actuation. Additional equipment is available for mechanical or electrical gas line
shut-off applications.
The detection portion of the fire suppression system allows for automatic
detection by means of specific alloy rated fusible links, which, when the temperature
exceeds the rating of the link, the link separates, allowing the regulated release to
actuate.
A system owner's guide is available containing basic information pertaining to
system operation and maintenance. A detailed technical manual is also available including
system description, design, installation, recharge, and maintenance procedures, plus
additional equipment installation and resetting instructions.
The system is installed and serviced by authorized distributors that are
trained by the manufacturer.
The basic system consists of an ANSUL AUTOMAN regulated release assembly which
includes a regulated release mechanism and a wet chemical storage tank housed within a
single enclosure. Nozzle blow-off caps, detectors, cartridges, agent, fusible links, and
pulley elbows are supplied in separate packages in the quantities need- ed for fire
suppression system arrangements.
Additional equipment includes remote manual pull station, mechanical and
electrical gas valves, pressure switches, and electrical switches for automatic equipment
and gas line shut-off. Accessories can be added such as alarms, warning lights, etc., to
installations where required.
Tanks can be used in multiple arrangements to allow for larger hazard coverage.
Each tank is limited to a listed maximum amount of flow numbers.
|
|
|
|
|
- Wet Chemical Agent
The extinguishing agent is a
potassium carbonate, potassium acetate-based formulation designed for rapid flame
knockdown and foam securement of grease related fires. It is available in plastic
containers with instructions for wet chemical handling and usage.
- Agent Tank
The agent tank is installed in a
stainless steel enclosure or wall bracket. The tank is deep drawn carbon steel finished in
red enamel. Tanks are available in two sizes: 1.5 gallon (5.7 L) and 3.0 gallon (11.4 L).
The tanks have a working pressure of 100 psi (6.9 bar), a test pressure of 300 psi (20.7
bar), and a minimum burst pressure of 600 psi (41.4 bar). The tank includes an
adaptor/tube assembly. The adaptor is chrome-plated steel with a 1/4 in. NPT female gas
inlet and a 3/8 in. NPT female agent outlet. The adaptor also contains a bursting disc
seal which prevents the siphoning of agent up the pipe during extreme temperature
variations.
- Regulated Release Mechanism
The regulated release
mechanism is a spring-loaded, mechanical/pneumatic type capable of providing the expellant
gas supply to one or two agent tanks, depending on the capacity of the gas cartridge used.
It contains a factory installed regulator deadset at 100 psi (6.9 bar) with an internal
relief of approximately 145 psi (10.0 bar). It has automatic actuation capabilities by a
fusible link detection system and remote manual actuation by a mechanical pull station.
The regulated release mechanism contains a release assembly, regulator, expellant gas
hose, and agent storage tank housed in a stainless steel enclosure with cover. The
enclosure contains knock-outs for 1/2 in. conduit. The cover contains an opening for a
visual status indicator. It is compatible with mechanical gas shut-off devices; or, when
equipped with a field or factory-installed switch, it is compatible with electric gas line
or appliance shut-off devices.
- Regulated Actuator Assembly
When more than two
agent tanks are required, the regulated actuator is available to provide expellant gas for
additional tanks. It is connected to the cartridge receiver outlet of the regulated
release mechanism providing simultaneous agent discharge. It contains a regulated actuator
deadset at 100 psi (6.9 bar) with an internal relief of approximately 145 psi (10.0
bar).The regulated actuator assembly contains a regulated actuator, regulator, expellant
gas hose, and agent tank housed in a stainless steel enclosure with cover. The enclosure
contains knockouts to permit installation of the expellant gas line.
- Discharge Nozzles - Each discharge nozzle is tested
and listed with the R-102 system for a specific application. Nozzle tips are stamped with
the flow number designation (1/2, 1, 2, and 3). Each nozzle must have a metal or rubber
blow-off cap to keep the nozzle tip orifice free of cooking grease build-up.
|
|
|
|
|
Applicable Standards: ULI listed under EX- 3470; ULC listed under
CEX-747; meets requirements of NFPA 96 (Standard for the Installation of
Equipment for the Removal of Smoke and Grease-Laden Vapors from Commercial Cooking
Equipment); NFPA 17A (Standard on Wet Chemical Extinguishing Systems).
|
|
|
|
|
|
|
|
|
|
|
|
Order all system components through your local authorized Ansul Distributor.
|
|
|
ANSUL FIRE PROTECTION
MARINETTE, WI 54143-2542
715-735-7411
|
|